Finding
HVIL is only as good as the connector and contactor chain behind it, which ties the safety function to a short list of connector, relay and pyrofuse makers
The loop starts in the connector: interlock pins in HV connectors from TE Connectivity, Amphenol, Aptiv, Rosenberger, Yazaki and China's AVIC Jonhon and Yonggui. It ends in the contactors, where China's Hongfa has become one of the largest makers of EV high-voltage DC relays alongside TE, Panasonic and Sensata.
The controller - usually the BMS, sometimes the vehicle control unit - reads the loop as a DC current or a pulse-width signal. Simple loops only see open or closed; resistance-coded and PWM schemes can tell an open circuit from a short to ground or battery and locate the fault. When the loop opens, the controller inhibits drive, opens the main contactors and triggers active discharge of the DC link. Re-energizing requires a controlled pre-charge sequence, never an automatic restart.
Standards treat interlocks as one accepted protection measure rather than a universal mandate: ISO 6469-3 and UN R100 for electrical safety, ISO 26262 for the functional safety of the monitoring logic, FMVSS 305 and UN R94/R95 for post-crash isolation, and China's GB 18384. HVIL sits alongside pyrofuses (Autoliv, Daicel, Littelfuse, Mersen, Eaton, Xi'an Sinofuse) that cut the pack in a crash, and the first-responder cut loop that disables the HV system from outside the vehicle.
How it works
Loop states and responses
| State | What happens | Typical response |
|---|---|---|
| Loop closed | All monitored connectors, covers and service plugs are seated | HV enable allowed if other checks pass |
| Loop interrupted | A connector, cover or disconnect changes state | Fault set, drive inhibited, contactors opened |
| Diagnostic confirmation | Controller separates transients from persistent opens | Fault latched, service code stored |
| Recovery | Loop restored and checks run | Pre-charge, then contactors close; no automatic re-energizing |
Designs
HVIL design approaches
| Approach | How it works | Strength | Tradeoff |
|---|---|---|---|
| Simple continuity loop | Open or closed DC loop | Cheap and simple | Cannot locate faults or detect shorts |
| Resistance-coded loop | Expected resistance per state | Identifies fault class | More validation work |
| PWM or current-source loop | Controller injects a signal and checks it returns | Detects shorts to ground or battery | Controller hardware and software cost |
| Staged-contact connector | HVIL pins break before power pins | Protects during unmating | Connector complexity |
Failure modes
How HVIL fails
| Failure | Cause | Desired response |
|---|---|---|
| Open circuit | Broken wire, unmated connector, pulled service plug | Fault and HV isolation |
| Intermittent opens | Vibration, partial seating, marginal routing | Debounced detection and clear service codes |
| Corrosion | Moisture and salt at connectors | Sealed connectors; trend monitoring |
| Short that masks an open | Pinched loop wire shorted to ground or battery | Signal-based loops that detect shorts |
| Logic error | Wrong thresholds or state handling | ISO 26262 validated software, fail-safe defaults |
Supply chain
HVIL supply chain
| Element | Role | Suppliers |
|---|---|---|
| Interlock-capable HV connectors | Monitored physical interface | TE, Amphenol, Aptiv, Rosenberger, Yazaki, AVIC Jonhon, Yonggui |
| Service disconnects | Manual isolation point with monitored state | TE, Amphenol, Littelfuse, Eaton |
| Contactors and HV relays | Physical de-energizing | Hongfa, TE, Panasonic, Sensata (Gigavac) |
| Pyrofuses | Crash and fault isolation | Autoliv, Daicel, Littelfuse, Mersen, Eaton, Xi'an Sinofuse |
| Controller and software | Reads loop, commands response | BMS suppliers and OEM in-house teams |
Sources
Sources and scope
- Scope
- HVIL High-Voltage Interlock
- Sources
- ISO 6469-3; UN R100; ISO 26262; FMVSS 305; GB 18384; supplier disclosures